山西煤炭干部管理学院机电班采区供电设计(矿山机电)
dD5点两相短路电流:
I2Dd5S=Uar2/22=1.2/0.269=2.231KA
(6)给桥式转载机供电支线电缆阻抗,查表得MYP3×25×1×10相位阻抗值r0=0.732Ω/KM,x0=0.088Ω/KM RW11=X0L11=0.732×0.04=0.0293Ω XW11=r0L11=0.088×0.04=0.0035Ω 短路电流计算
∑R=R′W+RT+R′W2+RW11+0.01
=0.00818+0.0135+0.0046+0.0293+0.01=0.0606Ω ∑X=X′SY+X′W+XT+XW3+XW11
=0.0288+0.00132+0.1072+0.0015+0.0035 =0.142Ω
Z=∑R2+∑X2=0.0662+0.1422=0.157Ω dD6点两相短路电流:
ISDd1(2)=Uar2/Z2=1.2/0.157=3.827KA
(7)给液压安全绞车供电支线电缆阻抗,查表得MYP3×25×1×10每相位阻抗值r0=0.732Ω/KM,x0=0.088Ω/KM RW12=X0L12=0.732×0.410=0.300Ω XW12=r0L12=0.088×0.410=0.036Ω 短路电流计算
∑R=R′W+RT+R′W2+RW12+0.01 =0.00818+0.0135+0.0046+0.3+0.01
第 31 页 共 44 页
山西煤炭干部管理学院机电班采区供电设计(矿山机电)
=0.336Ω
∑X=X′SY+X′W+XT+XW3+XW11
=0.0288+0.00132+0.1072+0.0015+0.0036 =0.1725Ω
Z=∑R2+∑X2 =0.3362+0.1752=0.379Ω dD7点两相短路电流:
IS(2)=Uar2/22=1.2/0.379=1.583KA
(8)q3变电站阻抗,查表得KBSG—500/0.69变电站阻抗电压U%=4%,负载损耗△PN=3.300W
RT=△PNU22N/S2N=3300×0.692/5002=0.0063Ω ZT=U%U22N/SN=0.4×0.692/0.5=0.3809Ω XT=ZT-RT=0.38092-0.00692=0.38091Ω
(9)干线电缆W17阻抗,查表得MYP3×50×1×10每相位阻抗值ro=0.380Ω/KM,x0=0.081Ω/KM RW17=X0L17=0.38×0.02=0.0076Ω XW17=r0L17=0.081×0.02=0.0016Ω RW18=X0L18=0.38×0.36=0.1368Ω XW18=r0L18=0.081×0.36=0.0292Ω
(10)给顺槽皮带运输机供电支线电缆阻抗,查表得MYP3×35×1×16每相位阻抗值r0=0.522Ω/KM,x0=0.084Ω/KM RW7=X0L7=0.084×0.07=0.0059Ω XW7=r0L7=0.522×0.07=0.0365Ω
第 32 页 共 44 页
山西煤炭干部管理学院机电班采区供电设计(矿山机电)
短路电流计算
(1)dD2点短路回路的总阻抗 ∑R=R′W+RT+R′W7+RW7+0.01 =0.00818+0.0063+0.0076+0.0365+0.01 =0.069Ω
∑X=X′SY+X′W+XT+XW7+XW7
=0.0288+0.00132+0.3809+0.0016+0.0059 =0.419Ω
Z=∑R2+∑X2=0.0692+0.4192=0.425Ω dD2短路电流:
ISdD2(2)=Uar2/Z2=0.69/2×0.425=0.812KA
(11)给顺槽皮带运输机照明综合支线电缆阻抗,查表得MYP3×4×1×4每相位阻抗值r0=4.66Ω/KM,x0=0.101Ω/KM RW6=X0L6=4.66×0.07=0.3262Ω XW6=r0L6=0.101×0.07=0.0071Ω dD12点短路回路的总阻抗 ∑R=R′W+RT+R′W7+RW76+0.01
=0.00818+0.0063+0.0076+0.3262+0.01=0.358Ω ∑X=X′SY+X′W+XT+XW7+XW6
=0.0288+0.00132+0.3809+0.0016+0.0059=0.419Ω Z=∑R2+∑X2 =0.3852+0.4192=0.551Ω dD12短路电流:
第 33 页 共 44 页
山西煤炭干部管理学院机电班采区供电设计(矿山机电)
I(2)SDd12=Uar2/22=0.69/2×0.551=0.626KA
(12)给上山皮带运输机支线电缆阻抗,查表得MYP3×35×1×16每相位阻抗值r0=0.522Ω/KM,x0=0.084Ω/KM RW5=X0L5=0.084×0.07=0.0059Ω XW5=r0L5=0.522×0.07=0.0365Ω dD1点短路回路的总阻抗
∑R=R′W+RT+R′W7+RW5+0.01+R′W18 =0.00818+0.0063+0.0076+0.0365+0.01+0.1368 =0.205Ω
∑X=X′SY+X′W+XT+XW17+XW5+XW18
=0.0288+0.00132+0.3809+0.0016+0.0059+0.0292 =0.448Ω
Z=∑R2+∑X2 =0.2052+0.4482=0.493Ω dD1短路电流:
I(2)Dd1=Uar2/2Z=0.69/2×0.493=0.7KA
(13)上山皮带运输机照明综保支线电缆阻抗,查表得3×4×1×4每相位阻抗值r0=4.66Ω/KM,x0=0.101Ω/KM RW4=X0L4=4.66×0.07=0.326Ω XW4=r0L4=0.101×0.07=0.007Ω dD13点短路回路的总阻抗
∑R=R′W+RT+R′W17+RW4+0.01+R′W18+0.01 =0.00818+0.0063+0.0076+0.326+0.1368+0.01
第 34 页 共 44 页
山西煤炭干部管理学院机电班采区供电设计(矿山机电)
=0.495Ω
∑X=X′SY+X′W+XT+XW17+XW4+XW18
=0.0288+0.00132+0.3809+0.0016+0.007+0.0292 =0.449Ω
Z=∑R2+∑X2 =0.3852+0.2=0.668Ω dD13短路电流:
IS(2)=Uar2/22=0.69/2×0.668=0.516KA
第八节 采区接地保护措施
井下保护接地系统是由主接地极、局部接地极、接地母线、接地导线和接地引线等组成.
井下保护接地网按<<煤矿安全规程>>第448~第453条规定执行. 第448条 36V以上和由于绝缘置换可能带有危险电压的电气设备的金属外壳,构架等必须有保护接地。
电气保护接地工作,应按煤炭工业部颁发的有关矿井保护接地装置的安装、检查与测定工作细则执行。
第449条 接地网上任一保护接地点测得的接地电阻值不得超过2Ω,每一个移动式和手持式电气设备同接地网之间的保护接地用的电缆芯线(或其他相当接地导线,一以下各条同)的电阻值不得大于1Ω。
第450条 所有电气设备的保护接地装置(包括电缆的铠装、铠皮、接地芯线)和局部接地装置都应同井下住接地接成一个总接地网。
第 35 页 共 44 页
百度搜索“77cn”或“免费范文网”即可找到本站免费阅读全部范文。收藏本站方便下次阅读,免费范文网,提供经典小说综合文库煤矿采区供电设计(1)(7)在线全文阅读。
相关推荐: