第七节 采区设备最小两相短路整定
一、10KV系统的平均电压Uar1=10.5KV,1140V系统的平均电压Uar2=1.2KV 1)各组件阻抗计算 (1)系统折算电抗: X1XY=U2/Sbn=1.22/so=0.0288Ω
(2)高压电缆W1折算阻抗,查表得MYP-3×35高压电缆n0=0.522Ω/KM;X0=0.084Ω/KM
x1w1=X0L1(Uar2/Uar1)2=0.084×1.2×(1.2/10.5)2=0.00132Ω R1w1=R0L1(Uar2/Uar1)2=0.522×1.2×(1.2/10.5)2=0.00818Ω (3)q1移动变电站阻抗。查表得KBSG2Y—500/1.2KV移动变电站,阻抗电压η%=4.5%,负载损耗△PN=3800W RT=△PNU22N/S2N=3800×1.22/5002=0.0218Ω 2T=U%U22N/SN=0.045×1.22/0.5=0.1296Ω XT=Z2T-R2T= 0.12962-0.02182=0.12774Ω
(4)干线电缆W2阻抗,查表WYP—3×95+1×16每相单位阻抗值r0=0.23Ω/KM'X0=0.076Ω/KM XW2=X0L2=0.076×0.02=0.0015Ω RW2=r0L2=0.236×0.02=0.0046Ω
(5)给采煤机供电的支线电缆阻抗,查表得MrP3×25+1×10+3×6每相单位阻抗值r0=0.732Ω/KM,X0=0.088Ω/KM
第 26 页 共 44 页
山西煤炭干部管理学院机电班采区供电设计(矿山机电)
XWB=X0LB=0.088×0.2=0.018Ω RWB=r0LB=0.732×0.2=0.146Ω 2)短路电流计算
(1)dD8点短路回路的总阻抗: ∑R=R′W+RT+R′W2+RW8+0.01 =0.00818+0.0218+0.0046+0.146+0.01 =0.1906Ω
∑X=X′Y+XW+XT+XW2+XWB
=0.0288+0.00132+0.12774+0.0015+0.018 =0.177Ω
Z= ∑R2+∑X2= 0.0662+0.1422 = 0.259 (2)dD8点两相短路电流: I2dD8S=Uar2/Z2=1.2/0.259=2.317KA
(3)给刮板输送机供电的支线电缆阻抗和采煤机一样。 短路电流计算dD13和d14点相同,
(4)给喷雾泵供电的线支线电缆阻抗,查表得MYP3×4+1×4每相单位阻抗值r0=4.66Ω/KM,X0=0.10/Ω/KM XW15=X0L15=0.101×0.006=0.0061Ω RW15=r0L15=4.66×0.006=02796Ω (5)短路回路的总阻抗: ∑R=R′W+RT+R′W2+RW15+0.01 =0.00818+0.0218+0.0046+0.146+0.01
第 27 页 共 44 页
山西煤炭干部管理学院机电班采区供电设计(矿山机电)
=0.324Ω
∑X=X′SY+X′W+XT+XW2+XW15
=0.0288+0.00132+0.12774+0.0061+0.0015 =0.1655Ω
(6)dD10点两相短路电流: I2dD8S=Uar2/22=1.2/0364=1.648KA
(7)给乳化液泵站供电的支线电缆阻抗和喷雾泵一样。 XW16=X0L16=0.101×0.01=0.0010Ω RW16=r0L16=4.66×0.01=0.0466Ω 1、短路回路的总阻抗: ∑R=R′W+RT+R′W2+RW16+0.01 =0.00818+0.0218+0.0046+0.0466+0.01 =0.0911Ω
∑X=X′SY+X′W+XT+XW2+XW16
=0.0288+0.00132+0.12774+0.0015+0.0010 =0.1601Ω
2、d11点两相短路电流Z=0.092+0.162=0.184Ω I2d11S=Uar2/22=1.2/2×0.184=3.260KA
3)G移动变电站阻抗,查表10—9得KBSGZK800/1.2KV移动变电站阻抗电压U%=6.0,负载损耗△PN=6000W RT=△PNU22N/S2N=6000×1.22/8002=0.0135Ω zT=U%U22N/SN=0.06×1.22/0.80=0.1080Ω
第 28 页 共 44 页
山西煤炭干部管理学院机电班采区供电设计(矿山机电)
XT==0.1072Ω
(1)干线电缆W2同W3相同
(2)给喷雾泵供电的线支线电缆阻抗,查表得MYP3×4×1×1.5每相位阻抗值r0=4.66Ω/KM,x0=0.101Ω/KM XW8=X0L80.101×0.04=0.004Ω RW8=r0L8=4.66×0.04=0.186Ω (3)短路电流计算
∑R=R′W+RT+R′W3+RW8+0.01 =0.00818+0.0135+0.0046+0.186+0.01 =0.222Ω
∑X=X′SY+X′W+XT+XW3+XW8
=0.0288+0.00132+0.1072+0.0015+0.004 =0.1428Ω
Z=∑R+∑X=0.2222+0.1432=0.263Ω dD3点两相短路电流:
I2dD3S=Uar2/22=1.2/0263=2.281KA
(4)给破碎机供电的支线电缆的阻抗,查表得MYP3×16 ×1×10每相位阻抗值r0=1.16Ω/KM,x0=0.090Ω/KM RW9=X0L9=1016×0.04=0.046Ω XW9=r0L9=0.009×0.04=0.0036Ω 短路电流计算
(1)dD4点短路回路的总阻抗
第 29 页 共 44 页
山西煤炭干部管理学院机电班采区供电设计(矿山机电)
∑R=R′W+RT+R′W2+RW9+0.01 =0.00818+0.0135+0.0046+0.01+0.0464 =0.0831Ω
∑X=X′SY+X′W+XT+XW3+XW9
=0.0288+0.00132+0.1072+0.0015+0.00036 =0.142Ω
Z=∑R+∑X=0.0832+0.1422=0.164Ω (2)dD4点两相短路电流: I2dD4S=Uar2/22=1.2/0.164=3.659KA
(5)给备用乳化液泵站供电的支线电缆的阻抗,查表得MYP3×4×1×1.5每相位阻抗值r0=4.66Ω/KM,x0=0.101Ω/KM RW10=X0L10=4.66×0.036=0.1678Ω XW10=r0L10=0.101×0.36=0.0364Ω 短路电流计算
(1)dD5点短路回路的总阻抗 ∑R=R′W+RT+R′W3+RW10+0.01 =0.00818+0.0135+0.0046+0.1678+0.01 =0.204Ω
∑X=X′SY+X′W+XT+XW3+XW10
=0.0288+0.00132+0.1072+0.0015+0.00364 =0.175Ω
Z=∑R2+∑X2=0.2042+0.1752 =0.269Ω
第 30 页 共 44 页