17 18 19 20 21 22 87 88 89 90 93 105 60.96 64.74 69.71 76.26 102.44 105 88 89 90 91 95 105 49.4 52.89 57.6 64.49 102.3 105
88 89 90 91 95 105 50.26 53.75 58.46 65.35 103.16 105 99 100 105 106 107 108 79.24 105 105 105 105 105 序ICV1&ICV2 号 流量% 开度% -2.75 -5 1 0 0 2 4 16.29 3 8 22.685 4 16 29.08 5 20 55.6 6 24 100 7 105 100 8 考虑到机组长期运行的经济性,在机组稳定运行半年以上后,可调整为顺序阀配汽方式,顺序阀曲线
如下表所示:
序号 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
CV1&CV4 流量% 开度% -5 -5 0 0 3.9 10.36 32.8 26.45 58.55 40.23 64.54 44.82 66.7 47.13 68.45 49.41 70.09 51.73 71.2 54.04 72.24 56.32 73.24 58.63 74.14 60.91 74.81 63.22 75.45 65.51 76.04 67.82 77.01 72.41 77.7 77 顺 序 阀 CV2 CV3 流量% 开度% 流量% 开度% -5 -5 -5 -5 0 0 0 0 77.7 0 91.97 0 79.67 10.36 93.47 10.36 81.26 12.64 94.19 12.64 85.1 19.54 95.47 17.23 87.82 26.45 96.57 21.82 89.12 31.04 97.37 26.45 90.05 35.64 98 31.04 90.46 37.92 98.24 33.32 90.77 40.23 98.46 35.64 91.04 42.54 98.67 37.92 91.51 47.13 98.86 40.23 91.91 51.73 99.03 42.54 92.03 54.04 99.26 47.13 92.33 60.91 99.42 51.73 92.6 70.13 99.58 56.32 92.67 77 99.66 58.63 16
19 20 21 22
79.67 81.26 82.63 100 86.22 95.41 100 100 93.47 94.19 94.84 100 90.81 100 100 100 99.86 99.95 99.96 100 65.51 72.41 81.6 100 混合阀切顺序阀的条件包括:55%额定负荷<机组负荷<85%额定负荷、保护限制未动作。 当机组解列或者遮断时,逻辑将自动切换回混合阀方式。
为了保证切换过程中机组运行平稳,切换速度不宜过快,出厂设置的切换时间为10min。并且在切换过程中不允许往回切。