华北水利水电学院毕业设计
S发电机G1:Xjs?X1G1?0.135?Sd1350.85?0.214 100135发电机G2:Xjs?0.749?发电机G3?6:
0.85?1.190 1004?135Xjs?0.652?0.85?4.142?3.45 故可做无限大电源处理。 100则发电机和系统供给的短路电流为:
''110kV系统:IS1*?11??9.174 X100.109100?38.382 (kA)
3?13.8 Is''1?9.174?''220kV系统:IS2*?11??0.738 X111.355100?3.088 (kA)
3?13.8 Is''2?0.738?135SG0.85?6.645 (kA) ?发电机G1: Id?3Ud3?13.8查运算曲线,对应Xjs?0.214
??1?5.29?6.645?35.151 (kA) ??1*?5.29 IG 有t = 0 时 IG t =2时 IG1(2)*?3.351 IG1(0.2)?3.351?6.645?22.267 (kA) t = 4 时 IG1(4)*?3.213 IG1(4)?3.213?6.645?21.350 (kA)
135SG0.85?6.645 (kA) ?发电机G2: Id?3Ud3?13.8查运算曲线,对应Xjs?1.190
??2?0.880?6.645?5.848 (kA) ??2*?0.880 IG 有t = 0 时 IG t = 2时 IG2(2)*?0.977 IG2(2)?0.977?6.645?6.492 (kA) t = 4 时 IG2(4)*?0.977 IG2(4)?0.977?6.645?6.492 (kA) 发电机G3?6:
第 23 页 共 59 页 华北水利水电学院毕业设计
'' IG3?6?0.241?26.581?6.406 (kA)
总的三相短路电流:
t = 0 时 I''f1?38.382?3.088?35.151?5.848?6.406?88.875 (kA) t = 2时 If1(2)?38.382?3.088?22.267?6.492?6.406?76.635 (kA) t = 4 时 If1(4)?38.382?3.088?21.350?6.492?6.406?75.718 (kA) 三相短路冲击电流
ish(f1)?2?1.9?35.151?2?1.8?(38.382?3.088?5.848?6.406)?231.175 (kA)
表1.1 f1点短路电流计算结果
短路电流(kA) 短路点 短路位置 冲击电流(kA) I?f?1 f1 110kV侧发电机G1 出口处 88.875 If1(2) 76.635 If1(4) 75.718 231.175 1.3 f2点短路
网络化简如下:
S120.028S250.106220kV10.09730.07940.051110kVf2G1-2G3-6
图1.5 f2点短路系统的等值电路图
11 X1?(XT1?XG)?(0.058?0.135)?0.097
22X2?XS1?0.028
第 24 页 共 59 页 华北水利水电学院毕业设计
X3?XAT2?XAT1??0.004?0.083?0.079
X4?11(XT2?XG)?(0.069?0.135)?0.051 44X5?XS2?XL?0.038?0.068?0.106
星型化三角得发电机和系统对短路点f1得转移电抗: 220kV系统: X6?X3?X5?发电机G3?6: X7?X3?X4?X3X40.079?0.051?0.079?0.051??0.168 X50.106X3X50.079?0.106?0.079?0.106??0.349 X40.051110kV系统:X2?0.028 发电机G1?2:X1?0.097
S120.028S260.349f270.16810.097G1-2图1.6 f2点短路时的转移电抗
G3-6
将转移电抗化为各电源对短路点的计算电抗:
2?135发电机G1?2: Xjs?0.097?0.85?0.308 1004?135发电机G3?6:Xjs?0.168?0.85?1.067 100则发电机和系统供给的短路电流为:
第 25 页 共 59 页 华北水利水电学院毕业设计
''110kV系统:IS1*?10011?17.930 (kA) ??35.714,Is''1?35.714?X20.0283?11510011?1.438 (kA) ??2.865, Is''2?2.865?X60.3493?115''220kV系统:IS2*?S发电机G1?2: Id?G?3Ud2?1350.85?1.595 (kA) 3?115查运算曲线,对应Xjs?0.308
??1?2*?3.615 IG??1?2?3.615?1.595?5.765 (kA) 有t = 0 时 IG t = 2时 IG1?2(2)*?2.934 IG1?2(2)?2.934?1.595?4.679 (kA) t = 4 时 IG1?2(4)*?2.968 IG1?2(4)?2.968?1.595?4.733 (kA)
S发电机G3?6: Id?G?3Ud4?1350.85?3.190 (kA) 3?115查运算曲线,对应Xjs?1.067
??3?6*?1.005 IG??3?6?1.005?3.190?3.205 (kA) 有t = 0 时 IG t = 2时 IG3?6(2)*?1.150 IG3?6(2)?1.15?3.190?3.699 (kA) t = 4 时 IG3?6(4)*?1.150 IG3?6(4)?1.150?3.190?3.669 (kA) 总的三相短路电流:
t = 0 时 I''f2?17.930?1.438?5.765?3.205?28.338 (kA) t =2时 I''f2(2)?17.930?1.438?4.679?3.669?27.716 (kA) t = 4 时 I''f2(4)?17.930?1.438?4.733?3.669?27.770 (kA) 三相短路冲击电流:
ish(f2)?2?1.85?5.765?2?1.8?(17.930?1.438?3.205)?72.533 (kA)
表1.2 短路电流计算结果
短路电流(kA) 短路点 短路位置 冲击电流(kA) 72.533 I?f?2 f2
110kV母线处 28.338 If2(2) 27.716 If2(4) 27.533 第 26 页 共 59 页 华北水利水电学院毕业设计 1.4 f3点短路
网络化简如下图所示:
图1.7 f3点短路时等值电路图
11 X1?(XT1?XG)?(0.058?0.135)?0.097
22X2?XS1?0.028
X3?XAT2?XAT1??0.004?0.083?0.079 X4?XG?0.135 X5?XT2?0.069
X6?XS2?XL?0.038?0.068?0.106
11X7?(XT2?XG)?(0.069?0.135)?0.068
33星型化三角为:
X8?X2?X3?X2X30.028?0.079?0.028?0.079??0.130 X10.097 X9?X1?X3?
X1X30.097?0.079?0.097?0.079??0.450 X20.028 第 27 页 共 59 页